NORDTEK DANMARK - Current Transformer AC1040, 40A - Low Cost - nordtek.se

Current Transformer AC1040, 40A - Low Cost

Low Cost - High Quality - 50/60Hz Current Transformer - Primary Measuring Current 40A


Applications
  • Sensing Overload Current
  • Ground fault detection
  • Metering
  • Analog to Digital Circuits
  Current Transformer AC1040, 40A




Electrical Specifications @ 20°C ambient

Electrical Specifications
 Primary Current   40A nom., 125A max
 Turns Ratio   1000:1 nominal
 Volt per Amp Ratio at 40A
 for 100 ohm load
  0.100 V/A
 Volt per Amp Ratio at 4A
 for 100 ohm load
  0.098 V/A
 DC Resistance at 20°C   49.3 ohms
 Dielectric Withstanding Voltage
 (Hi-pot)
  4KVrms
 
Mechanical Specifications
 Case   Polycarbonate
 Encapsulant   Epoxy
 Flammability   Conforms to UL94-VO
 Terminals   Pins Ø 1.0mm
 Marking   TALEMA
  Date Code (W/Y)
  AC1040
  Dot at start pin
 Approximate Weight   47.3 grams
 Tolerance   ± 0.2mm
   
Environmental Specifications
 Storage Temperature   -55°C to 130°C
 Insulation Resistance   100 megohms min.
 



  Output Volts vs Input Current & Dimensions   %RE vs RL at Rated primary current & Excitations Curve  



#top#